Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C16-1365
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location: SUITE E15A 3RD FLOOR
Work Description: TENANT IMPROVEMENT TO INCLUDE STRUCT,ARCH, ELEC, MECH, PLBG-GJS
INSPECTION FEES ARE DUE BEFORE ANY PERMIT ISSUANCES PER GJS 6/16/2016
10 Inspections added 06/20/16 - AJC
Status: Closed
Project Name: VICTORIA'S SECRET
Review Type: Structural
Result: Correction
Result Date: 5/18/2016 12:07:49 PM

Comments:

 Code SectionReview CommentStatus
1AMC 23.15.1704.1.4Local amendment:
Unless otherwise approved by the building official, special inspectors shall be pre-qualified and approved by the building official before performing special inspection activities on any project within the Municipality. Special inspectors shall obtain pre-approval for each category of inspection they wish to perform.
Please provide a letter from the Owner or Special Inspection Agency stating that the Owner has retained the Agency to provide required special inspections.

2_
Refer to Sheet A00.00, Detail E/S03.01. The code study incorrectly notes the construction type of the building as Type II-B; the mall is actually of Type I construction. The details note partition bracing to structure and deck, both of which will be protected by spray-applied fire-resistant material. Please coordinate with the architect on how the existing fire-resistance ratings will be maintained with the connections to deck/structure.
Reference: IEBC Section 702.1 (Section 603.1)


3_
Refer to Detail N/S03.01. The use of fire-retardant treated plywood is not permitted for Type I construction. Please revise by deleting reference.
Reference: IEBC Section 701.2 (Section 602.4)





Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS