Permit Number: C16-1365
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location: SUITE E15A 3RD FLOOR
Work Description: TENANT IMPROVEMENT TO INCLUDE STRUCT,ARCH, ELEC, MECH, PLBG-GJS
INSPECTION FEES ARE DUE BEFORE ANY PERMIT ISSUANCES PER GJS 6/16/2016
10 Inspections added 06/20/16 - AJC
Status: Closed
Project Name: VICTORIA'S SECRET
Review Type: Electrical
Result: Approved
Result Date: 4/26/2016 10:33:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

6/20/2016

the comment are addressed on the plans. APPROVED



Electrical Comment

 



Reviewed by: David Abuobaid                                                  Permit #: C16-1356



Phone: 343-8333                                                                       Date:
4/26/2016



Fax:     249-7775                                                                      



Email:  AbuobaidDH@muni.org



Permit Manager: Bob Parker



Phone: 343-8391



Email:  Parkerrw@muni.org



Project: Victoria’s
Secret (Fax: 614-545-4555)



____________________________________________________________________________________



1. The following comments based on the 2014
National Electrical Code (NEC) must be resolved before a permit is issued. The
approval of plans and specifications does not permit the violation of any
section of the NEC or any federal, state or local regulations.



 



2.  CIRCUIT DIRECTORY OR CIRCUIT INDENTIFICATION
ON FLOOR PLAN & PANEL SCHEDULES:



Sheet E05.01 (Panel
Schedules and Floor Plans Circuit Identifications). Panel schedule have many
circuits named sales area TK, Video monitor, transition rcpt. cashwrap IG, hand
steamer, hand, dryer, rolling grill, etc. Please note that these circuits
should be individually identified with their locations on floor plans and on
the panel schedules according to NEC 408.4 for circuit identifications.



 



3. AVAILABLE FAULT CURRENT:



Sheet E05.01 (Field Marking -
Available Fault Current). Please verify that the main service has and marked
with the calculation of the available fault current. NEC Section 110.24
requires that service equipment be legibly marked in the field with maximum
available fault current. The field markings shall include the date the fault
current calculation was performed and be of sufficient durability to withstand
the environment impact.



                                                                            
                                                                                                                                                                                                                                                                                                                             



4.  TRANSFORMER DISCONNECTING MEANS:



Sheet E05.01 (Line Diagram –
Transformer Disconnecting Mean Location). NEC Section 450.14 requires the
transformer have a disconnecting means located either in sight of the
transformer or in a remote location. When located in the remote location, the
disconnecting means shall be lockable and shall be field marked to reference
the transformer location. Please address..



 



5.  TRANSFORMERS MOUNTING (STRUCTURAL REVIEW)



Sheet E05.01 (Transformers Structural Seismic
Calculations). Provide structural, seismic calculations and fastening details
for the transformer including engineers stamp and signature, for structural review
on a deferred submittal basis.
Refer to Anchorage Administrative
Code AAC 23.10.104.8.1. Please address.



 



6.  When the above comments have been addressed,
please update the electrical plans at the MOA Plans Review Office with three
(3) sets of revised electrical pages to include clouded changes, electrical
engineers stamp and signature.      



 