Architectural Comments
Reviewed by: David Abuobaid Permit #: C16-1336
Phone: 343-8333 Date:5/2/2016
Fax: 249-7775
Email: AbuobaidDH@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: Parkerrw@muni.org
Project: KAYJEWELERS (Fax: no fax provided)
____________________________________________________________________________________
1. The following comments based on the 2012 InternationalBuilding Code (IBC) must be resolved before a permit is issued. The approval ofplans and specifications does not permit the violation of any section of the IBCor any federal, state or local regulations.
2. CODE INFORMATION:
Sheet A1 (Code Data). Please address thefollowing:
(A) Construction type is not IIB, It is type III-B.
3. SECURITY GRILL:
SheetA1.0. Please address the security grilles per IBC section 402.13 requirements.
4. SINK EXPOSED PIPES AND SURFACES:
Sheet A-4. The water supply and drainpipesunder the sink are exposes. ICC/ANSI A117.1-2003 Section 606.6 requires watersupply and drainpipes under the sink to be insulated or configured to protectagainst contact with sharp edges or abrasive surfaces. Please address
5. When the above comments have been addressed,please update the architectural plans at the MOA Plans Review Office with three(3) sets of revised electrical pages to include clouded changes, architecturestamp and signature.