Reviewed by: Bergstrom, Leigh W. Permit #: C15-2170
Phone: 343-8326 Date: 4/04/2015
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: VANS
Review Number: 369735
1) STATUS: 12-24-15 Comments to be addressed. 3-18-2016 COMMENTS TO BE ADDRESSED. 4-04-2016 APPROVED.
2) The following commentsbased upon the 2009 International Building Code (IBC) must be resolved before apermit is issued. The approval of plans and specifications does not permit theviolation of any section of the IBC or any federal, state or local regulations. RESOLVED 3-18-2016.
3) G-0.0 Applicable Codes ADA requirements are currently being reviewed under the 2003 ICC/ANSI A117.1. Please include. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
4) G-0.0 The 4th Avenue Mall construction type is "I-B", not "II-B". RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
5) G-0.0 Provide the fire-resistance rating for building elements for "I-B" construction per IBC Table 601. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
6) G-1.1 Division 06: Wood and Plastic Paragraph 2B states "All dimensional lumber to be fire retardant with U.L. rating non-combustible." Such treated wood is still considered combustible. Please address. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
7) G-1.1 The floor/ceiling assemblies have a 2-hour rating. Provide clarification to address maintaining the 2-hour rating protection at abandoned penetrations from demolition and any new penetrations such as for plumbing, electrical conduit or attachments. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
8) G-1-1 Existing beams and columns have a 2-hour protective wrap or spray coating. Provide clarification for providing repairs to any damage which may be found. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
9) HC-1.1 The standard "Disabled Access Details" needs to include the 33"-36" to top of gripping surface for the horizontal grab bars at water closets. (ICC/ANSI A117.1-609.4) RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
10) A-0.1 Rear service exit door #5, comment #10 specifies a 20 minute rated door. This is located on a 1-hour rated exit passageway and requires a 1-hour door per IBC Table 715.4. RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
11) A-1.2 The 33"-36" dimension for the horizontal grab bar at the water closet is measured to the top of the gripping surface, not centerline of the grab bar. (ICC/ANSI A117.1-609.4) RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.
12) 5/A-1.3 & 8/A-2.2 Provide structural and seismic calculations plus fastening details for the storage areas above the toilet room and the fitting room to include engineers stamp and signature for structural review on a deferred submittal basis. RESOLVED 3-18-2016.
13) A-4.2 Combustible materials (wood) are not permitted in Type I construction (IBC 602.2). Provide a code path that allows these applications that are shown. (Please note that fire retardant treated wood is still considered combustible). 3-18-2016 UNRESOLVED. THIS "SOFFIT" AREA WOULD BE CONSIDERED TO BE "SET OUT CONSTRUCTION" PER IBC *803.11.2 WHICH WOULD REQUIRE CLASS "A" FINISH MATERIALS OR THE WOOD MATERIALS (CLASS "C") WITH GWB BACKING OR SPRINKLER INSIDE AND OUT. RESOLVED PER RE-SUBMITTAL RECEIVED 4-01-2016.
14) When the above commentshave been addressed please update the plans at the MOA Plans Review Office withthree sets of revised architectural pages to include clouded changes, architectsstamp and signature.
RE-SUBMITTALS ARE TO BEDIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1) RESOLVED 4-04-2016.