Permit Number: C16-1276
Permit Type: Commercial Building Permit - None BldgAlter
Address: 9138 ARLON ST Anchorage
Location:
Work Description: Comm T/I to include move door openings, plumb/mech/electric and med gas - BWP
Status: Issued
Project Name: BTY DENTAL
Review Type: Fire
Result: Correction
Result Date: 3/24/2016 12:02:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Provide full sheet code analysis on all 3 plan sets.

2_
Provide / indicate detail on architectural/structural plans indicating one hour wall for medical gas room; include detail of opening (door) AND one hour shaft enclosure for supply and exhaust ducts. IFC 3006.2-3006.2.3.

3_
Indicate in code study amount of medical gas to be stored as this room is being extended. If exceeds amounts of IFC Table 2703.1 as indicated in summary, it must be in accordance with the IBC for high hazard Group H occupancies. IFC 3006.2

4_
Please indicate on plans location, size and type of fire extinguisher to be provided within 75' of all areas of unit.