Permit Number: C15-2170
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: Comm T/I: retail tenant improvement of mercantile structure within existing mall; inlcudes elec, plbg, mech for Ste D37A / tb

Status: Closed
Project Name: VANS
Review Type: Fire
Result: Correction
Result Date: 4/7/2016 1:21:00 PM

Comments:

 Code SectionReview CommentStatus
1_
Sht. A-3.1 - Fixture shelf VN 024 does not appear to allow 36' clear aisle width and Fixture VN -006-6 does not allow for a clear and continuous path to the means of egress (required 2nd exit.). Indicate on plans exit widths as required per IFC 1017.2. Revise plans as required to show compliant clear exit width/path provided.

2_
Required 2nd exit -Plans do not indicate exit access /egress through stockroom meets provision as indicated for IFC 1014.2, exception 2. Revise plans to indicate will meet all requirements or revised to provide compliant exit route.