Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-2170
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: Comm T/I: retail tenant improvement of mercantile structure within existing mall; inlcudes elec, plbg, mech for Ste D37A / tb

Status: Closed
Project Name: VANS
Review Type: Architectural
Result: Correction
Result Date: 3/18/2016 4:44:27 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:


Reviewed by: Bergstrom, Leigh W.                                             Permit #: C15-2170



Phone: 343-8326                                                                           Date: 3/18/2015



Fax: 249-7615



Email: BergstromLW@muni.org



Permit Manager: Tony Barganier



Phone: 343-8339



Email: BarganierTA@muni.org



Project: VANS



Review Number: 368547






1) STATUS:   12-24-15 Comments to be addressed.        3-18-2016 COMMENTS TO BE ADDRESSED.



 



2) The following comments
based upon the 2009 International Building Code (IBC) must be resolved before a
permit is issued. The approval of plans and specifications does not permit the
violation of any section of the IBC or any federal, state or local regulations.     RESOLVED 3-18-2016.




3) G-0.0 Applicable Codes          ADA requirements are currently being reviewed under the 2003 ICC/ANSI A117.1. Please include.               RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.





4) G-0.0            The 4th Avenue Mall construction type is "I-B", not "II-B".              RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




5) G-0.0            Provide the fire-resistance rating for building elements for "I-B" construction per IBC Table 601.         RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




6) G-1.1 Division 06: Wood and Plastic          Paragraph 2B states "All dimensional lumber to be fire retardant with U.L. rating non-combustible." Such treated wood is still considered combustible. Please address.                     RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.         



7) G-1.1            The floor/ceiling assemblies have a 2-hour rating. Provide clarification to address maintaining the 2-hour rating protection at abandoned penetrations from demolition and any new penetrations such as for plumbing, electrical conduit or attachments.             RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




8) G-1-1            Existing beams and columns have a 2-hour protective wrap or spray coating. Provide clarification for providing repairs to any damage which may be found.                   RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




9) HC-1.1          The standard "Disabled Access Details" needs to include the 33"-36" to top of gripping surface for the horizontal grab bars at water closets. (ICC/ANSI A117.1-609.4)        RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




10) A-0.1           Rear service exit door #5, comment #10 specifies a 20 minute rated door. This is located on a 1-hour rated exit passageway and requires a 1-hour door per IBC Table 715.4.               RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




11) A-1.2           The 33"-36" dimension for the horizontal grab bar at the water closet is measured to the top of the gripping surface, not centerline of the grab bar. (ICC/ANSI A117.1-609.4)           RESOLVED PER RE-SUBMITTAL RECEIVED 3-18-2016.




12) 5/A-1.3 & 8/A-2.2             Provide structural and seismic calculations plus fastening details for the storage areas above the toilet room and the fitting room to include engineers stamp and signature for structural review on a deferred submittal basis.           RESOLVED 3-18-2016.




13) A-4.2            Combustible materials (wood) are not permitted in Type I construction (IBC 602.2). Provide a code path that allows these applications that are shown. (Please note that fire retardant treated wood is still considered combustible).         3-18-2016 UNRESOLVED. THIS "SOFFIT" AREA WOULD BE CONSIDERED TO BE "SET OUT CONSTRUCTION" PER IBC *803.11.2 WHICH WOULD REQUIRE CLASS "A" FINISH MATERIALS OR THE WOOD MATERIALS (CLASS "C") WITH GWB BACKING OR SPRINKLER INSIDE AND OUT.



14) When the above comments
have been addressed please update the plans at the MOA Plans Review Office with
three sets of revised architectural pages to include clouded changes, architects
stamp and signature.

RE-SUBMITTALS ARE TO BE
DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH
A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS