Permit Number: C15-2191
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location:
Work Description: TENANT IMPROVEMENT-GJS
Status: Closed
Project Name: PACSUN
Review Type: Structural
Result: Approved
Result Date: 2/19/2016 7:22:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Please address the following comments:
  1. Special Inspection - Please provide a letter from the special inspection agency for the post installed anchors.
  2. See the cross braces as shown in detail 9 and 9A. Show the overall brace height (currently it shows "varies") and elevations from the floor to the start and end of the brace. This will allow the inspectors to verify proper installation.
  3. Sheet A530, note 11 calls out "flash skim" for the area under the proposed racks. Please verify and note on the plans th maximum thickness of topping and adjust the length of the post installed anchor, if required, to maintain minimum embedment depth.