Permit Number:
X16-1061
Permit Type:
Commercial Building Permit - ChangeOrdr BldgAlter
Address:
E 800 DIMOND BLVD Anchorage
Location:
Work Description:
Alt/Means to Arch and Fire - BWP
Status:
Closed
Project Name:
Change Order of Bldg App C15-2085
Review Type:
Fire
Result:
Correction
Result Date:
1/22/2016 3:12:00 PM
Comments:
Code Section
Review Comment
Status
1
_
Provide cut sheet showing proposed locking mechanism for insuring sliding doors are locked open. Locking mechanism shall be such that at no time can the doors be closed and locked by customers.
2
_
Provide signage above door- Door to be locked open while space is occupied.
3
_
If approved, make changes to all 3 sets of plans showing correct configuration.