Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-2130
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 320 5TH AVE Anchorage
Location: SUITE 355 THIRD FLOOR
Work Description: TENANT IMPROVEMENT-GJS
Status: Closed
Project Name: FAMOUS FOOTWEAR
Review Type: Fire
Result: Correction
Result Date: 1/7/2016 10:50:00 AM

Comments:

 Code SectionReview CommentStatus
1_
Please revise plans to indicate in plans fire extinguisher locations; to be placed within 75' of all areas, to be mounted with tops no higher than 5 ft above finished floor. Include classification type/size to be provided; must be adequate to hazard. Indicate signage to be provided to identify locations as required for extinguishers may be obscured due to racks. Due to staffing levels, Fire Inspectors inspect to approved plans only; extinguishers must in installed and in place per approved plans at time of inspection to receive certificate of occupancy. IFC Section 906.

2_
Sht. A3.0 - Please identify exit path for requried 2nd exit. It appears there is an exit sign at the area marked "No work" but no other identifier provided. Please indicate to ensure this is not storage but exit corridor, if it is such. IFC 1014.2

3_
Code study Sht. A1.0 indicates no sprinkler modification s to be made; Sht. A3.0 notes sprinkler coverage to confirm and submitted under separate cover for review and permit. Sprinkler & fire alarm separate deferred permit submittals with plans by fire protection contractors and not approved under this permit. Ensure sprinklers evaluated to be adequate coverage based upon commodity class. Provide documentation of same to fire inspector at time of fire final inspection to receive Certificate of Occupancy. IFC 105.4.2.1

4_
Plans do not indicate identifying suite number. Please indicate on plans, to be applied to both front and rear entrances. IFC 505.1




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS