Work Description:
Elimination of Door #1007B between electrical room 1ME007 & 1ME008; see attached RFI-260 / tb
Status:
Closed
Project Name:
Change Order of Bldg App C13-1177
Review Type:
Fire
Result:
Approved
Result Date:
12/7/2015 8:19:30 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
Documents submitted incomplete. Please include documentation (schematic, with letter) from Engineer / design professional that this switch gear is not part of the EPS emergency appurtenances and does not require the two hour separation as originally installed and approved – to be reviewed and approved also by Electrical Plan Reviewer.
Advisory Information:
Approved at counter - 90 min. double door added.