Permit Number: C15-2088
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: New Comm T/I to include plumb/mech/electric - BWP
Status: Closed
Project Name: PORK AND PICKLE RESTAURANT
Review Type: Architectural
Result: Correction
Result Date: 11/23/2015 3:12:00 PM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Bergstrom, Leigh W.                                                 Permit #: C15-2088

Phone: 343-8326                                                                              Date: 11/23/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Bob Parker 

Phone: 343-8391

Email: ParkerRW@muni.org

Project: Pork and Pickle Restaurant

Review Number: 363907

 

1) STATUS:   11-23-15 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) Provide structural and seismic calculations plus fastening details for the Overhead Roll-down Grilles 38 & 42/ID9.3 and the Soffits 26, 27 &35/ID9.2 to include engineers stamp and signature, for structural review on a deferred submittal basis.

 

4) CS Governing Codes           The 2011 NEC is the National Electric Code not the National Energy Code.

 

5) 30/ID9.2         Type I kitchen hoods that penetrate the ceiling plus the attached grease duct shall be enclosed from the point of penetration to the outlet terminal. (IMC 507.10 & 506.3.10) Provide clarification.

 

6) ID9.2         Wood and plywood are not permitted in Type I construction per IBC 602.2.

 

7) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)

          

 

 

 