Permit Number: C15-2085
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Commercial T/I to include Electrical only - AJC
Status: Issued
Project Name: CRICKET WIRELESS
Review Type: Fire
Result: Correction
Result Date: 11/20/2015 11:13:18 AM

Comments:

 Code SectionReview CommentStatus
1_
Indicate on plans location of fire extinguisher within 75' ft.  Indicate size, type and class; top to be mounted no higher than 5 ft above finished floor.  IFC 906.1

2_
No hardware or door schedule indicated on plans.  Indicate door and hardware to be provided on doors.  IFC 1008.1.9.3/ IBC  Sec. 402.

3_
Plans do not clearly reflect location of store within mall.  Please indicate on plans.  IFC 105.4.2.

4_
Plan sht. 2A does not appear to apply for layout of store proposed.  Exit signs do not appear to be adequately placed.  Please revised to indicate location of exits in direction of exit path.  IFC 1011.1