Reviewed by: Bergstrom, Leigh W. Permit #: C15-2071
Phone: 343-8326 Date: 11/19/2015
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Andrew Earp
Phone: 343-8338
Email: Earpal@muni.org
Project: KConoco Phillips ANO 08 & 07 CD-5 Group
Review Number: 363839
1) STATUS: 11-19-15 Comments to be addressed.
2) The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
3) P1 & P2 Public use lavatories L-1 & L-2 require an ASSE 1070 point of use mixing valve per UPC 413.1.
4) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature. RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT. (23.10.104.8.1)