Permit Number: C15-1876
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: Comm T/I; tenant improvement for Starbucks @ baggage claim; includes elec,plbg, mech / tb
Status: Closed
Project Name: STARBUCKS
Review Type: Fire
Result: Approved
Result Date: 10/22/2015 2:25:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Code study  Sht. A-1 conflicts with general notes indicating no fire extinguisher to be provided.  Indicate on plans location/size/class of fire extinguisher for this location within booth.  Must have current/compliant inspecton tag.

2_Resolved
Sprinkler coverage within this location may require adjustment due to remodel; not approved under this submittal.  Indicate on plans sprinkler system /fire alarm components to be adjusted by contractor permitted with State of Alaska for work on fire protection systems as required.  Install certification verifying work performed to be provide to fire inspector on site at fire final inspection.




Advisory Information:

approved at counter 10/22/15-plans redlined to reflect changes.