Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X15-2184
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: Elimination of Door #1007B between electrical room 1ME007 & 1ME008; see attached RFI-260 / tb
Status: Closed
Project Name: Change Order of Bldg App C13-1177
Review Type: Fire
Result: Correction
Result Date: 10/19/2015 9:43:39 AM

Comments:

 Code SectionReview CommentStatus
1_
Documents submitted incomplete.  Please include documentation (schematic, with letter) from Engineer / design professional that this switch gear is not part of the EPS emergency appurtenances and does not require the two hour separation as originally installed and approved – to be reviewed and approved also by Electrical Plan Reviewer.   




Advisory Information: