Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1161
Permit Type: Commercial Building Permit - None BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description:

3,150 sq ft comm bldg and bulk fuel tank / tb **Master file tank farm & controls bldg**

C15-1215 780 sq ft new truck loading/fuel station bldg; C15-1216 Bulk fuel tank & retaining wall

MOA & FIRE - 1/2 size; FIELD full size

Status: Expired
Project Name: POA BULK TERMINAL DELTA WESTERN
Review Type: Architectural
Result: Approved
Result Date: 10/23/2015 8:56:32 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved

ARCHITECTURAL DRAWINGS

Please provide a code study and Architectural Drawings that are stamped and signed by an architect licensed in Alaska as required by the Alaska State Statutes section 08.48.221. Reference AMC section 23.10.104.8. A full architectural review has not been provided.

 

Comment remains. MOA does not provide variances to Alaska State Statutes. WAB - 8/6/2015

 



2_Resolved

CONSTRUCTION TYPE

Reference sheets SG-01 and SG-05 of the drawings. The type of construction has been indicated as type IIB, and yet there are wood walls shown on sheet SG-05. Combustible material is permitted in Type IIB construction in limited conditions. This does not appear to be one of the conditions in which it is permitted. Reference IBC section 603.1.

 

Comment remains. The response appears to indicate no wood; however the drawings have not been modified to show this. WAB - 8/6/2015

 