Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: X15-2120
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: 3555 SHARON GAGNON LN Anchorage
Location:
Work Description: Alt Means & Methods:  change design of residential kitchen hood to include residential fire suppression system / tb
Status: Closed
Project Name: Change Order of Bldg App C15-1783
Review Type: Fire
Result: Approved
Result Date: 10/2/2015 11:52:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
A separate permit submittal for fire plan review of the fire suppression system by a State Permitted Contractor is required.  IFC 105.4.2




Advisory Information:

10/2/15-Alternate means for use of residental hood suppression system in lieu of commercial fire suppression hood system approved by Fire Marshal Hill.  Per Fire Marshal HIll, provisions are: limited use of kitchen & highly supervised cooking only.  (Ref. Master Permit # C15-1783)

Note:  Deferred submittal of fire suppression equipment system- to be tied into building fire alarm and submit for permit for system.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS