Reviewed by: Bolen, Wayne A. Permit #: C15-1922
Phone: 343-8072 Date: 10/8/2015
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Bob Parker
Phone: 343-8391
Email: ParkerRW@muni.org
Project: Ted Stevens Airport Passenger Gate
Review number: 361160
____________________________________________________________________________________
PERMIT STATUS
10/8/2015 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. Please clarify why the spiral ties in the foundation do not meet a minimum 3" pitch as required by ACI 318-08 section 7.10.4.3. Please also indicate an additional 1 1/2 turns of the spiral at the ends of the spiral unit as required by ACI 318-08 section 7.10.4.4.
2. The anchor bolt design in the calculations provided indicate that it's a preliminary design, and the drawings indicate the anchor bolts are by other. Please provide final design of the anchor bolts the and final anchor bolt requirements on the drawings. The permit can not be approved without this information. Reference AAC section 23.10.104.8.
3. Please provide a letter from the Owner indicating who they will be hiring to provide the special inspections for this project. The special inspectors must be licensed by MOA in the types of inspections to be performed. Reference IBC section 1703.1.
Please provide a written response to the comments and include one copy of additional or revise calculations and two copies of additional or revise drawings.
All submittals should be sent to the permit manager.