Master File: Comm T/I: interior remodel for North Lobby remodel; includes elec, plbg, mech / tb
Plans are reviewed under Master File C15-1781 / tb
RESOLVED by Alternate Means & Methods- Residential hood suppression system approved by Fire Marshal Cleo Hill in lieu of Type I commercial suppression hood system (Ref. Permit X15-2120).
Sht. A12.1- Door schedule does not reflect type of hardware to be provided on egress side of door from kitchen. Revise plans to indicate hardware identified as existing lockset. Door shall be readily openable from the egress side without the use of key, special knowledge or effort to exit. IFC 1008.1.9