Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1782
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3701 RESIDENTIAL DR Anchorage
Location:
Work Description:

Master File: Comm T/I: interior remodel for East Lobby remodel; includes elec, plbg, mech / tb

Plans are reviewed under Master File C15-1781 / tb

Status: Closed
Project Name: UAA RCR EAST LOBBY REMODEL
Review Type: Fire
Result: Approved
Result Date: 10/2/2015 12:37:10 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Sht. A12.1- Door schedule does not reflect type of hardware to be provided on egress side of door from kitchen.  Revise plans to indicate hardware identified as existing lockset.  Door shall be readily openable from the egress side without the use of key, special knowledge or effort to exit.  IFC 1008.1.9

2_Resolved

RESOLVED by Alternate Means & Methods- Residential hood suppression system approved by Fire Marshal Cleo Hill in lieu of Type I commercial suppression hood system (Ref. Permit X15-2119). 

Type I hood & with fire suppression system required for communal cooking equipment / kitchen. (estimated 300 occupants- 75 per floor.)  Revise plans to Indicate requirement to provide type I hood / suppression system throughout as needed, including code study.  Separate permit required for fire suppression system; indicate on plans as required.  IFC 105.4.2



3_Resolved
Sht. A0.1 Code study references code under which building was constructed but is not applicable code under which current work is being accomplished.  Revise plans to reflect reference codes for construction of this project in code study. IFC 105.4.2.




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS