Master File: Comm T/I: interior remodel for East Lobby remodel; includes elec, plbg, mech / tb
Plans are reviewed under Master File C15-1781 / tb
RESOLVED by Alternate Means & Methods- Residential hood suppression system approved by Fire Marshal Cleo Hill in lieu of Type I commercial suppression hood system (Ref. Permit X15-2119).
Type I hood & with fire suppression system required for communal cooking equipment / kitchen. (estimated 300 occupants- 75 per floor.) Revise plans to Indicate requirement to provide type I hood / suppression system throughout as needed, including code study. Separate permit required for fire suppression system; indicate on plans as required. IFC 105.4.2