Register
My Neighborhood
Jobs
Contact Us
Home
Residents
Businesses
Government
Visitors
Departments
Public Safety
Transportation
Recreation
ePay
Maps
Services A-Z
Muni.org
>
Departments
>
Development Services
> Permit Information & Inspection Request
Click Here To Go Back To Permit Information
Permit Number:
C15-1781
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
3601 RESIDENTIAL DR Anchorage
Location:
Work Description:
Master File: Comm T/I: interior remodel for West Lobby remodel; includes elec, plbg, mech / tb
Status:
Closed
Project Name:
UAA RCR WEST LOBBY REMODEL
Review Type:
Fire
Result:
Resubmit
Result Date:
9/22/2015 4:57:06 PM
Comments:
Code Section
Review Comment
Status
1
_
Sht. A12.1- Door schedule does not reflect type of hardware to be provided on egress side of door from kitchen. Revise plans to indicate hardware identified as existing lockset. Door shall be readily openable from the egress side without the use of key, special knowledge or effort to exit. IFC 1008.1.9
2
_
Type I hood & with fire suppression system required for communal cooking equipment / kitchen. (estimated 300 occupants- 75 per floor.) Revise plans to Indicate requirement to provide type I hood / suppression system throughout as needed, including code study. Separate permit required for fire suppression system; indicate on plans as required. IFC 105.4.2
3
_
Sht. A0.1 Code study references code under which building was constructed but is not applicable code under which current work is being accomplished. Revise plans to reflect reference codes for construction of this project in code study. IFC 105.4.2.
Advisory Information:
ADA Compliance
Privacy Statement & Disclaimer
Employee Search
eNewsletter
RSS
OFFICIAL WEB SITE OF THE MUNICIPALITY OF ANCHORAGE, ALASKA
632 West 6th Avenue, Anchorage, Alaska 99501