Permit Number: X15-2083
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: 2801 DEBARR RD Anchorage
Location:
Work Description: AS-BUILT PANEL SCHEDULES - TC
Status: Closed
Project Name: Change Order of Bldg App C13-1177
Review Type: Electrical
Result: Correction
Result Date: 9/28/2015 9:57:46 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Electrical Comments

 

Reviewed by: David Abuobaid                                                               Permit #: C15-1177

Phone: 343-8333                                                                                    X15-2083

Fax:     249-7775                                                                                   Date: 9/28/2015

Email:  AbuobaidDH@muni.org

Permit  Manager: Tony Barganier

Phone: 343-8339

Email:   BarganierWA@muni.org

Project: Alaska Regional (Fax: 208-360-3148)

____________________________________________________________________________________

1. The following comments based on the 2011 National Electrical Code (NEC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the NEC or any federal, state or local regulations.

 

2.  ESSENTIAL POWER SYSTEM:

Sheet E6.01 to Sheet E6.04. The plans contain only panel schedule. Please provide one-line diagram and show the essential power system that include life safety equipment, transfer switches, and specify the life safety panel schedules and review emergency panel schedule for allowable load. Refer to Anchorage Administrative Code AAC 23.10.104.8.1. Please address.

 

3.  When the above comments have been addressed, please update the electrical plans at the MOA Plans Review Office with three (3) sets of revised electrical pages to include clouded changes, electrical engineers stamp and signature.   

 