Permit Number: C15-1894
Permit Type: Commercial Building Permit - None BldgAlter
Address: 2751 DEBARR RD Anchorage
Location:
Work Description: Comm T/I: demo entry & walls, frame new walls, tape and finish, finishes, acoustical ceiling, casework, includes elec, plbg, mech / tb
Status: Closed
Project Name: WOMEN'S CARE OF ALASKA
Review Type: Architectural
Result: Correction
Result Date: 9/29/2015 11:30:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C15-1894

Phone: 343-8326                                                                           Date: 9/29/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Women's Care of Alaska

Review Number: 360733

 

1) STATUS:   9-29-15 Comments to be addressed.

 

2) The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 

3) A2          Glazing details and door schedules are located within the written specifications which were not provided. Provide a copy of the written specifications.

 

4) A4          Provide listed top of wall slip joint assembly details for the rated wall assembly Types "E" & "F".

 

5) 8/A9       The staff shower and bench must meet ADA standards per ICC/ANSI A117.1 Chapter 6.

 

6) When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised architectural pages to include clouded changes, architects stamp and signature.

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

 