Permit Number: C15-1781
Permit Type: Commercial Building Permit - None BldgAlter
Address: 3601 RESIDENTIAL DR Anchorage
Location:
Work Description: Master File: Comm T/I: interior remodel for West Lobby remodel; includes elec, plbg, mech / tb
Status: Closed
Project Name: UAA RCR WEST LOBBY REMODEL
Review Type: Fire
Result: Correction
Result Date: 8/28/2015 6:18:25 PM

Comments:

 Code SectionReview CommentStatus
1_
Sht. A12.1- Door schedule does not reflect type of hardware to be provided on egress side of door from kitchen.  Revise plans to indicate hardware identified as existing lockset.  Door shall be readily openable from the egress side without the use of key, special knowledge or effort to exit.  IFC 1008.1.9

2_
Type I hood & with fire suppression system required for communal cooking equipment / kitchen. (estimated 300 occupants- 75 per floor.)  Revise plans to Indicate requirement to provide type I hood / suppression system throughout as needed, including code study.  Separate permit required for fire suppression system; indicate on plans as required.  IFC 105.4.2

3_
Sht. A0.1 Code study references code under which building was constructed but is not applicable code under which current work is being accomplished.  Revise plans to reflect reference codes for construction of this project in code study. IFC 105.4.2.