Permit Number: X15-1423
Permit Type: Commercial Building Permit - ChangeOrdr BldgAdd
Address: 2500 MINNESOTA DR Anchorage
Location:
Work Description: DEFERRED SUB:  vibration & seismic controls for HVAC / tb
Status: Closed
Project Name: Change Order of Bldg App C14-1705
Review Type: Structural
Result: Approved
Result Date: 9/1/2015 1:15:17 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

DESIGN OF SCREWED ATTACHMENTS

Reference the calculations. Where the design of the screws is for combined tension and shear, it appears that the combined loading check has been taken as TD/T+VD/V < 1.2. Please provide substantiating documentation showing this equation is appropriate for combined tension and shear in a screw. AISI S100-07 section E4.5 appears to indicate a different equation. This equation deals specifically with combined shear and pull over. For other limit states please use the unity check unless there is documentation showing another method is appropriate.