Permit Number: X15-1618
Permit Type: Commercial Building Permit - ChangeOrdr BldgCombo
Address: 1700 HILLCREST DR Anchorage
Location:
Work Description: DEFERRED SUB:  operable wall structural steel / tb
Status: Closed
Project Name: Change Order of Bldg App C14-1704
Review Type: Structural
Result: Correction
Result Date: 8/31/2015 8:35:34 AM

Comments:

 Code SectionReview CommentStatus
1_

LATERAL RESTRAINT

Reference the calculations. It appears that the intent is to try and restrain the partition by developing a couple through two bolts into a beam flange. Please clarify how this is done. Based on the system the top of the wall will just translate, and not allow any type of rotation in the beam which would be required to develop the tension/compression couple shown. The loading in the rods would include a tension a compression component, but also a bending component. The tension and compression component would be from the rods resisting the beam rotation. The bending component would be from the lateral translation of the bottom of the rods as compared to the ones at the top. It also doesn't appear as if the loads consider include the shear from the lateral load. It is also not clear how the plate length was determined when determining the capacity of the web of the beam. Why is this value 6*12? The effective web length would not be based on the spacing between the rods. Please clarify. Reference IBC section 1604.4.






Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C14-1704

Phone: 343-8072                                                                       Date: 8/31/2015

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: West High School Addition and Renovations

Review Number: 358976

____________________________________________________________________________________

 

PERMIT STATUS

8/31/2015 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.

 

All submittals should be sent to the permit manager.