Permit Number: C15-1687
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: MISC. SMALL TENANT DEMISING WALLS AND SANITARY SEWER LINE - TC
Status: Issued
Project Name: SHELL IMPROVEMENTS
Review Type: Fire
Result: Approved
Result Date: 7/29/2015 11:56:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved

RESOLVED 8/18/15- Revised plans submitted indicating corridor with approved widths provided for tenant improvement area/core & shell  units 171-172, 174-177-approved; not exit passageway; code study, life safety egress plan included. (Exception: area not included in this permit shown on egress plan, west side of mall indicates existing condition exceeds travel distances; to be addressed in future remodel/separate permit).  YNJAEGGE

Proposed Tenant Lease Space Suite 175 exits into passageway that does not provide the min. required minimum 20 ft. width per IFC 402.5.1.  Revise plans to show minimum requirement provided.