RESOLVED 8/18/15- Revised plans submitted indicating corridor with approved widths provided for tenant improvement area/core & shell units 171-172, 174-177-approved; not exit passageway; code study, life safety egress plan included. (Exception: area not included in this permit shown on egress plan, west side of mall indicates existing condition exceeds travel distances; to be addressed in future remodel/separate permit). YNJAEGGE
Proposed Tenant Lease Space Suite 175 exits into passageway that does not provide the min. required minimum 20 ft. width per IFC 402.5.1. Revise plans to show minimum requirement provided.