Permit Number: F15-1337
Permit Type: Commercial Trade Permit - New Fire
Address: 4000 CREDIT UNION DR Anchorage
Location:
Work Description: (44) DEVICES
Status: Closed
Project Name: AK USA DRY PIPING REPLACEMENT
Review Type: Fire System
Result: Correction
Result Date: 8/6/2015 7:34:00 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

Municipality of Anchorage

 

Building Safety Division

 

Fire System Comments

 

Reviewed by: Mark Warren                                                         Permit #: F15-1337

Phone: 267-4992                                                                        Date: 8/6/2015

Fax: 249-7393

Email: warrenmj@muni.org

Permit Manager: Andrew Earp

Phone: 343-8338

 

Email: earpal@muni.org

Project: Ak USA dry system                          

Review Number: 356960

____________________________________________________________________________________

 

PERMIT STATUS: Corrections

1)       Provide a cross section elevation view of the new and existing pipe.

2)       NFPA requires all dry sprinkler heads to either tested or replaced every 10 years. It appears re-using existing heads is not in the best interest of the customer.

 

All submittals should be sent to the permit manager.