Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1448
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Comm T/I:  interior remodel of storage space to include new finishes and minor electrical and mechanical / tb
PERMIT CANCELLED, NO WORK DONE UNDER THIS PERMIT-GJS
Status: Cancelled
Project Name: H&M RETAIL INTERIOR REMODEL
Review Type: Mechanical
Result: Approved
Result Date: 7/27/2015 9:33:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C15-1448

Phone: 343-8326                                                                           Date: 7/27/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: H & M Retail 

Review Number: 356857

 

STATUS:   6-5-15 Comments to be addressed.     7-27-15 APPROVED.

 

The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 



2_Resolved

Provide structural and seismic calculations plus fastening details for AHU-1 to include engineers stamp and signature, for structural review on a deferred submittal basis.



3_Resolved
M-230      Clarify note #27 at AHU-1.

4_Resolved
M-230     Clarify the outside air duct size (Ref note #33).

5_Resolved
M-230     Clarify the location of CP-1.

6_Resolved
M-230     With reference to note #25, didn't the existing bathroom have an exhaust fan with existing duct work? If running new exhaust ducting up through the roof is necessary, please note that this area is a mezzanine in the basement, requiring two floor/ceiling assembly penetrations as well as the roof/ceiling assembly penetration. Since this building is Type "I-A" construction, fire dampers will be required at the penetrations. Please clarify.

7_Resolved
M-230       Also with reference to note #25, the schedule and plan indicate a ceiling mounted exhaust fan, while the note calls for a roof mounted exhaust fan. And where is the janitors closet that was mentioned?




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter