Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1448
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Comm T/I:  interior remodel of storage space to include new finishes and minor electrical and mechanical / tb
PERMIT CANCELLED, NO WORK DONE UNDER THIS PERMIT-GJS
Status: Cancelled
Project Name: H&M RETAIL INTERIOR REMODEL
Review Type: Fire
Result: Approved
Result Date: 8/4/2015 10:22:58 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Add an aditional fire extinguisher (FE) within the stock room as the travel distance to the single FE is not within 75ft of all portions of the room.

2_Resolved
Add two exit signs within the mezzanine stock room, one directly above the exit access door leading to the corridor and the other at the intersection of colum/line B/8.5.  The shelving layout and odd shape of the room and the fact the travel distance is at or possibly over 100ft would provide a clearly noted direct route to the single exit.  A double sided exit sign orientated parallel with 8.5 and the exit access door is recommended.

3_Resolved
Resolutions to the above comments may be deferred.  Contact your MOA Permit Techinian (Tony Bargainer) and refer to this comment that corrections are still required but fire is "OK" to issue permit to begin work".  This review is only for the mezzanine stockroom area.




Advisory Information: