Electrical transformers seismic restraint
Seth Wilde - 801-569-5450
Reviewed by: Bolen, Wayne A. Permit #: C13-1177
Phone: 343-8072 Date: 7/17/2015
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Regional Electrical Transformers Seismic Restraint
Review Number: 354285
____________________________________________________________________________________
PERMIT STATUS
7/17/2015 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
1. TRANSFORMER MOUNTED ABOVE THE FLOOR
Please provide the following information about the transformer mounted above the floor:
A. Connection of transformer to frame.
B. Connection of the B-Line struts to the wall.
C. Connection of the frames to the floor.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.
All submittals should be sent to the permit manager.