Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1161
Permit Type: Commercial Building Permit - None BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description:

3,150 sq ft comm bldg and bulk fuel tank / tb **Master file tank farm & controls bldg**

C15-1215 780 sq ft new truck loading/fuel station bldg; C15-1216 Bulk fuel tank & retaining wall

MOA & FIRE - 1/2 size; FIELD full size

Status: Expired
Project Name: POA BULK TERMINAL DELTA WESTERN
Review Type: Fire
Result: Approved
Result Date: 7/27/2015 4:47:20 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Sht. SG-01 - Clarification needed on if there a specific commodity to be stored in the warm storage building.  Please identify commodity. 

2_Resolved
SG-01- Clarification needed for Exterior lock set A to be applied to exit door.

3_Resolved
Sht. SG04- Address not indicated on building of elevation page.  Provide building identification; numerals must be contrasting and large enough to be visible from roadway for first responders.  IFC 505.1

4_Resolved
Sht. SG-04 - Knox Box required on building for fire dept. access.  Revise plans to show knox box on front of building; to be mounted no higher than 6 ft at main entrance.  Contact AFD 267-4901 to schedule with captain on duty to have keys to main entrance and all control areas / knox cap installed once box is mounted.  IFC 506.1

5_Resolved
No code study was provided for the methanol storage tank/loading station.  Please provide a full code study and architectural drawings stamped and signed by an arcitect licensed in Alaska as required by Alaska State Statute Sec. 08.48.221.  Ref. AMC Sec.  23.10.104.8.  A full review has not been provided.

6_Resolved

6/29/15- REVIEW COMMENT- Revised civil plans provided, however some detail lacking.  Indicate on plans dimensions showing actual fire dept. access road widths provided; fire flow for hydrants in code study or notes; required # of hydrants and fire flow, and actual fire flow & hydrants provided.  Approved to begin construction of containment wall this date.  YNJAEGGE

 6/25/15 REVIEW COMMENT- Reviewed fire dept. access w/design professional.  Revise civil plan to indicate gate at NE fence to allow for fire dept. access / Relocate parking to provide for 26' FD access; indicate knox padlock or knox box at all gates.  Relocate snow storage from roadway identified as fire dept. access route to provide 26' clear width. 

Provide civil drawings showing fire dept. access at all points to building and tank.  Hydrant must be available and accessible within 600 ft to all exterior.  Show/indicate width of gate on plans.  IFC 507.5.1/ Appendix C & D.  A full plan review has not been provided.

 






Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS