Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1161
Permit Type: Commercial Building Permit - None BldgNew
Address: 1612 ANCHORAGE PORT RD Anchorage
Location:
Work Description:

3,150 sq ft comm bldg and bulk fuel tank / tb **Master file tank farm & controls bldg**

C15-1215 780 sq ft new truck loading/fuel station bldg; C15-1216 Bulk fuel tank & retaining wall

MOA & FIRE - 1/2 size; FIELD full size

Status: Expired
Project Name: POA BULK TERMINAL DELTA WESTERN
Review Type: Mechanical
Result: Correction
Result Date: 6/29/2015 3:32:00 PM

Comments:

 Code SectionReview CommentStatus
1_

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C15-1161

Phone: 343-8326                                                                           Date: 6/29/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: POA Bulk Terminal Delta Western

Review Number: 355229

 

 

STATUS:   3-24-15 Comments to be addressed.         6-29-15 COMMENTS TO BE ADDRESSED.

 

The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.



2_Resolved

Sheets MG-01 & MG-02 are missing.

 



3_
4/M-09           "Horizontal upper combustion air ducts shall not slope downward toward the source of combustion air" (IFGC 304.11.6) and shall be sized per IFGC 304.6.2.          6-29-15 UNRESOLVED. THE INTENT OF THE CODE IS TO NOT CREATE A HEAT TRAP. 

4_

NEW 6-29-15    Provide structural and seismic calculations plus fastening details for BLR-101 to include engineers stamp and signature, for structural review on a deferred submittal basis.






Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS