Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1436
Permit Type: Commercial Building Permit - None BldgNew
Address: W 410 40TH AVE Anchorage
Location:
Work Description: 1200 sq ft new comm bldg / tb
Status: Closed
Project Name: ALASKA USA FEDERAL CREDIT UNION
Review Type: Private Development Site Civil Review
Result: Correction
Result Date: 6/23/2015 11:39:35 AM

Comments:

 Code SectionReview CommentStatus



Advisory Information:

 

OK for Footing & Foundation ONLY, MG 6-8-15.    Other grading work outside of the building footprint such as storm drain and final grading are not approved.  By the developer going forward with the F&F the floor elevation will be set prior to approval of a grading & drainage plan stamped by a civil engineer that may result in significant increased costs to the developer to resolve site specific challenges to preparing an approvable site grading & drainage plan.

 

Correction, MG 6-8-15, 6-23-15.

 

1.  Ref. C2.0;  Please clarify where the swale that runs north along the west property line discharges into a drainage facility.  "Proposed drainage systems shall convey drainage into an established natural watercourse or an existing storm drainage facility" DCM 2.2.D.6.  Resolved, MG 6-23-15.

 

2.  PDCIVIL comments may be incomplete pending further submittals.

 

3.  Ref. C2.0, 12" CPEP connection to 36" CMP;  A manhole shall be installed at major junctions places where there are changes in vertical or horizontal alignment, and at locations where there are changes in pipe size or shape.  2007 DCM 2.7.D.1.  MG 6-23-15.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS