Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1346
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

T.I.: REMODEL FOR RESTAURANT. NEW FINISHES AND EQUIPMENT - TC

CONTRACTOR TO PAY INSPECTION FEES BEFORE PERMIT CAN BE ISSUED

Status: Closed
Project Name: ROUND TABLE PIZZA
Review Type: Architectural
Result: Approved
Result Date: 6/11/2015 12:07:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                         Permit #: C15-1458

Phone: 343-8326                                                                         Date: 6/05/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Round Table Pizza

Review Number: 352548

 

5-15-15 Comments to be addressed.     6-05-15 COMMENTS TO BE ADDRESSED.

The following comments based upon the 2009 International Building Code (IBC) must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC or any federal, state or local regulations.

 



2_Resolved

Provide structural and seismic calculations plus fastening details for the suspended ceiling soffit to include engineers stamp and signature, for structural review on a deferred submittal basis.



3_Resolved
G1.00      Except for the tower, the rest and older part of the Dimond Center Mall is Type "III-B" construction. Redo the Code Study to reflect the Type "III-B" construction.

4_Resolved
G1.00      The Dimond Center Vicinity Map shows the tenant improvement on Level 2 while the floor plans indicate Level 1 with exterior exit doors to grade. Please clarify.        6-05-15 UNRESOLVED. THE PERFECT CUP AND CINEMAS ARE LOCATED ON THE SECOND FLOOR. IF THIS TENANT IMPROVEMENT IS INDEED ON THE SECOND FLOOR, WE ARE NOT AWARE OF ANY EXTERIOR LANDING WITH STAIRS TO GRADE. IF THERE IS PROVIDE CLARIFICATION ON THE PLANS. 

5_Resolved
A1.00      It appears that all of the glass walls for Party Room 117 require safety glazing per IBC 2406.4.6 & 2406.4.7. Please clarify.        6-05-15 UNRESOLVED. THE REQUIREMENT FOR THE SAFETY GLAZING MUST BE ANNOTATED ON THE PLANS.

6_Resolved
FS1.00        There is not sufficient room at door #7 to Party Room #117 to provide ADA access or exiting. (ICC/ANSI A117.1-404.2.3)




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter