Permit Number: X15-1561
Permit Type: Commercial Building Permit - ChangeOrdr BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Deferred to Struct - Revised podium attachments - BWP
Status: Closed
Project Name: Change Order of Bldg App C15-1015
Review Type: Structural
Result: Approved
Result Date: 7/8/2015 1:03:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Please provide at least one copy of the details sealed by the EOR that meet the minimum text size of 3/32 in. per MOA Policy AG.39.

http://www.muni.org/Departments/OCPD/development/BSD/Policies/Policyag39.pdf



2_Resolved
The details for the podium framing call for plywood sheathing. This building is of Type I-A construction, which restricts the use of combustible construction is non-structural applications. Please note the requirement of fire-retardant-treated sheathing, or provide alternate non-combustible sheathing.
Reference: IBC Section 603.1 Item 25