Permit Number:
C15-1470
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
E 530 BENSON BLVD Anchorage
Location:
Work Description:
Comm T/I: tenant improvement for Indigo Tea; includes elec, plbg, mech / tb
Status:
Issued
Project Name:
INDIGO TEA
Review Type:
Fire
Result:
Correction
Result Date:
6/9/2015 2:02:25 PM
Comments:
Code Section
Review Comment
Status
1
_
The permit application shows the proposed use as an A2. Since the previous use was a Group M the type of permit should reflect a "Change of Use" .
2
_
Show on plans both the number and location of maximum occuppant load signage as required per IBC 1004.3
3
_
Room 111 is shown as a storage room. IBC 1014.2 would not allow egress thru this room unless you meet all conditions of 4 exception 2 particularly 2.4.
4
_
It appears that occuppants will be required to pass through a storage area of another tenant. IBC 1014.2.1, to include the exception, does not allow this. Even if allowed the painted exit pathway on the floor would not be compliant with 1014.2. It apears that an egress corridor is required.
5
_
Provide electrical plans showing locatons of emergency light and exit fixtures. Include both existing & new. It appears that a directional exit sign will be required between space 101 & 104.
6
_
Provide door hardware details. All doors leading to the 2nd exit (105, 111, & the existing south side exterior door) shall be equipped with panic hardware.