Refer to Geotechnical Memo dated 5/11/2015. The memo notes the capacity of the piles. Please address the following:a. No input or output was provided to show what the vertical capacities are based on.b. Please note the overlying granular soils may not necessarily be able to provide any appreciable lateral capacity; the peat has no quantifiable shear capacity, and the overlying granular soils may actually load the piles. Please provide justifying documentation on lateral capacity, including any analysis with input and output.Reference: IBC Section 1810.3.3
Please note the following seismic design information on the plans, regardless of whether seismic loads govern the design of the lateral-force-resisting system of the building: