Permit Number:
C15-1436
Permit Type:
Commercial Building Permit - None BldgNew
Address:
W 410 40TH AVE Anchorage
Location:
Work Description:
1200 sq ft new comm bldg / tb
Status:
Closed
Project Name:
ALASKA USA FEDERAL CREDIT UNION
Review Type:
Fire
Result:
Approved
Result Date:
5/27/2015 12:00:00 AM
Comments:
Code Section
Review Comment
Status
1
_
Resolved
E1- Emergency generator system not approved under this permit. A separate fire permit for generator system testing is required. Submit for separate Fire systems permit. IFC 105.4.2.1
5/29/15-RESOLVED-Plans redlined at counter to indicate generator has an on-premises fuel supply sufficient for 2 hour full demand operation of the system incorporated separate permit to be submitted. YNJaegge
2
_
Resolved
Sht. E3-Verify source/location of required on premises fuel supply for emergency diesel generato- if intention is to have diesel fuel storage tank on site indicate location on plans. IFC 604.2.14.1.1
5/29/15-RESOLVED-Plans redlined at counter to indicate generator has an on-premises fuel supply sufficient for 2 hour full demand operation of the system incorporated. YNJaegge
3
_
Resolved
Additional requirements may result from response to review comments.YNJAEGGE
5/29/15-RESOLVED-Plans redlined at counter to indicate generator has an on-premises fuel supply sufficient for 2 hour full demand operation of the system incorporated. YNJaegge