Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1346
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

T.I.: REMODEL FOR RESTAURANT. NEW FINISHES AND EQUIPMENT - TC

CONTRACTOR TO PAY INSPECTION FEES BEFORE PERMIT CAN BE ISSUED

Status: Closed
Project Name: ROUND TABLE PIZZA
Review Type: Fire
Result: Approved
Result Date: 6/4/2015 3:14:55 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Provide occuppant load signage as required per IBC 1004.3.  Show location on the plans.

2_Resolved
Adjust exit signage & emergency lighting near F/24.  When exiting from party room 117 area you can not see the exit signage at the main entrance area.  Also the emergency light fixture behind the bar most likely will not provide sufficient light along the floor between the bar stools & booths, area 114.

3_Resolved
Adjust the code study to reflect the updated construction type of the building, common path, allowable area, .  What is the reference to common path of 100ft for a "B Occuppancy" under section 1014.3?  For an "A Occuppancy" this is limited to 75 ft.

4_Resolved
Verify that the infilling or blocking of existing door 1 in delivery area 107 will be done in such a manner that the finished result does not clearly resemble a door.  If door is to be left in place remove hardware and provide signage indicating "Door Blocked" "Not an Exit". 




Advisory Information:

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter