Permit Number: C15-1450
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: T.I.  NEW RESTARAUNT; NEW EQUIPMENT- MECHANICAL UPGRADE; ELECTRICAL UPGRADE, SPRINKLER UPGRADE.  AE
Status: Closed
Project Name: SUSHI ON THE FLY
Review Type: Plumbing
Result: Approved
Result Date: 6/30/2015 12:21:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C15-1450

Phone: 343-8326                                                                            Date: 6/30/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Andrew Earp

Phone: 343-8338

Email: Earpal@muni.org

Project: Sushi On The Fly

Review Number: 352506

 

STATUS:   6-15-15 Comments to be addressed.     6-30-15 APOPROVED.

 

The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 

 



2_Resolved
2/M11      The 3-compartment sink requires a center waste outlet (UPC 1001.2) with vented P-trap (1014.1.1) and a vented flow control fitting (UPC 1014.2.1).




Advisory Information:

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised plumbing pages to include clouded changes, engineers stamp and signature.                                                   RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.