Permit Number: C15-1450
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description: T.I.  NEW RESTARAUNT; NEW EQUIPMENT- MECHANICAL UPGRADE; ELECTRICAL UPGRADE, SPRINKLER UPGRADE.  AE
Status: Closed
Project Name: SUSHI ON THE FLY
Review Type: Mechanical
Result: Approved
Result Date: 6/30/2015 12:24:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                               Permit #: C15-2162

Phone: 343-8326                                                                            Date: 6/30/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Andrew Earp

Phone: 343-8338

Email: Earpal@muni.org

Project: Sushi On The Fly

Review Number: 352504

 

STATUS:   6-15-15 Comments to be addressed.       6-30-15 APPROVED.

 

The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 



2_Resolved

Provide structural, seismic and wind load calculations as applicable, plus fastening details for MAU-1, KH-1 and Dishwasher #10 Exhaust Hood to include engineers stamp and signature, for structural review on a deferred submittal basis.



3_Resolved
M8      Dishwaser #10 is not an undercounter type and would appear to require a Type II hood overhead. Please clarify.




Advisory Information:

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                              

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.