Permit Number:
C15-1450
Permit Type:
Commercial Building Permit - None BldgAlter
Address:
W 5000 INTERNATIONAL AIRPORT RD Anchorage
Location:
Work Description:
T.I. NEW RESTARAUNT; NEW EQUIPMENT- MECHANICAL UPGRADE; ELECTRICAL UPGRADE, SPRINKLER UPGRADE. AE
Status:
Closed
Project Name:
SUSHI ON THE FLY
Review Type:
Fire
Result:
Correction
Result Date:
6/15/2015 4:08:51 PM
Comments:
Code Section
Review Comment
Status
1
_
Show locations of all fire extinguishers (FE) within the maximum allowed 75 ft travel of any point within the work area. Include existing, new, or relocated FE's. The reconfiguring of the larger space and the travel path out of the smaller space may conflict with previous Fe distribution.
2
_
The relocating of fire alarm strobes may create gaps in the coverage. At final inspection provide an installers certification for any work done to the fire alarm system to inclde demo, relocate or adding of speaker/strobes.