Muni.org > Departments > Development Services> Permit Information & Inspection Request
Click Here To Go Back To Permit Information

Permit Number: C15-1448
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description: Comm T/I:  interior remodel of storage space to include new finishes and minor electrical and mechanical / tb
PERMIT CANCELLED, NO WORK DONE UNDER THIS PERMIT-GJS
Status: Cancelled
Project Name: H&M RETAIL INTERIOR REMODEL
Review Type: Mechanical
Result: Correction
Result Date: 6/5/2015 10:25:00 AM

Comments:

 Code SectionReview CommentStatus
1_

Reviewed by: Bergstrom, Leigh W.                                             Permit #: C15-1448

Phone: 343-8326                                                                           Date: 6/05/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: H & M Retail 

Review Number: 352443

 

STATUS:   6-5-15 Comments to be addressed.

The following comments based on the 2009 International Building, Mechanical and Fuel Gas Codes must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the IBC, IMC, IFGC or any federal, state or local regulations.

 



2_

Provide structural and seismic calculations plus fastening details for AHU-1 to include engineers stamp and signature, for structural review on a deferred submittal basis.



3_
M-230      Clarify note #27 at AHU-1.

4_
M-230     Clarify the outside air duct size (Ref note #33).

5_
M-230     Clarify the location of CP-1.

6_
M-230     With reference to note #25, didn't the existing bathroom have an exhaust fan with existing duct work? If running new exhaust ducting up through the roof is necessary, please note that this area is a mezzanine in the basement, requiring two floor/ceiling assembly penetrations as well as the roof/ceiling assembly penetration. Since this building is Type "I-A" construction, fire dampers will be required at the penetrations. Please clarify.

7_
M-230       Also with reference to note #25, the schedule and plan indicate a ceiling mounted exhaust fan, while the note calls for a roof mounted exhaust fan. And where is the janitors closet that was mentioned?




Advisory Information:

When the above comments have been addressed please update the plans at the MOA Plans Review Office with three sets of revised mechanical pages to include clouded changes, engineers stamp and signature.                                              

RE-SUBMITTALS ARE TO BE DIRECTED TO THE ATTENTION OF THE PERMIT MANAGER WITH A LETTER OF RESPONSE ADDRESSING EACH COMMENT.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter