Permit Number: C15-1445
Permit Type: Commercial Building Permit - None BldgAlter
Address: W 900 5TH AVE Anchorage
Location:
Work Description: T.I.: REMOVE GLASS PANELS, DEMO CURB, CONSTRUCT 2 PARTITION WALLS CUT IN 2 DOORS - TC
Status: Issued
Project Name: BRADLEY REID & ASSOCIATES
Review Type: Fire
Result: Approved
Result Date: 5/20/2015 10:10:00 AM

Comments:

 Code SectionReview CommentStatus
1_Resolved
Sheet A1 - change in exiting (also indicated in item 3 of Project notes).  No scale provided to verify egress requirements.  Provide revised plans indicating scale.

2_Resolved
Plans submitted are sheet A-1 only; does not include electrical plan. Provide electrical plans for this project.  IFC 1004.1

3_Resolved
Sht. A1 does not indicate square footage of area.  Revise plans to indicate same.  IFC 105.4.2

4_Resolved
Sht. A-1 does not provide occupant load.  Provide revised plans / code study showing occupant load for this area to determine occupant load requirements.  IFC 1004.1

5_Resolved
Please clarify if the stair in the south east area serves as exit component for the other 6 floors that the change of exiting provides adequate exiting for those converging floors and occupant load of 1st floor.  It appears this may have created exiting through tenant spaces and may not be permitted by code IEBC Sec.705. Please identify / clarify code path on code study of plans including locking of doors 102.  

6_Resolved
Is fire extingluisher on south side of building within 75 of all areas?  Please indicate on plans meets travel distance.  IFC 906.3.1

7_Resolved
Submittal responses may result in additional fire plan review comments. 