TENANT IMPROVEMENT - TC
SHELL AND STORE FRONT C15-1149
CONTRACTOR TO PAY FOR INSPECTION FEES
RESOLVED 6/15/15 - Plans redlined to correct information. YNJAEGGE
5/21/15 COMMENT- Type 10ABC indicated on plans is not adequate size. Min. 2A10BC required.
Show size, type, & location of fire extinguishers (FE's) as required per IFC 906 to include one on the mezzanine. FE's shall be located along the path of egress at or near exit doors. Provide either a mounting detail or note to insure height requirements are met. The note on sheet CS1 referencing to coordinate exact locations with the fire marshall needs to be done as part of the plan review process. field adjustments may occurr providing compliance with IFC 906 is maintained.