Permit Number: C15-1346
Permit Type: Commercial Building Permit - None BldgAlter
Address: E 800 DIMOND BLVD Anchorage
Location:
Work Description:

T.I.: REMODEL FOR RESTAURANT. NEW FINISHES AND EQUIPMENT - TC

CONTRACTOR TO PAY INSPECTION FEES BEFORE PERMIT CAN BE ISSUED

Status: Closed
Project Name: ROUND TABLE PIZZA
Review Type: Plumbing
Result: Approved
Result Date: 5/12/2015 2:52:00 PM

Comments:

 Code SectionReview CommentStatus
1_Resolved

Reviewed by: Bergstrom, Leigh W.                                         Permit #: C15-1458

Phone: 343-8326                                                                         Date: 5/12/2015

Fax: 249-7615

Email: BergstromLW@muni.org

Permit Manager: Tommy Cornell

Phone: 343-8181

Email: CornellTA@muni.org

Project: Round Table Pizza

Review Number: 351412

 

STATUS:   4-29-15 Comments to be addressed.             5-12-15 APPROVED.

The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.

 



2_Resolved
M2.1        The cast iron or copper DWV waste piping and branch fitting that serve FS-1 at the soda dispenser are not compatible with the disposed byproducts. (UPC 313.4)

3_Resolved

M2.1     The 3-compartment sink requires a center waste outlet (UPC 1001.2) with separate vented P-trap (UPC 1014.1.1).



4_Resolved
1, 2 & 4/M2.2      The 3/4" gas branch serving WH-1 (125 MBH @ 100 feet)and the 1" gas main serving the oven and WH-1 (260 MBH @ 100 feet) appear to be undersized per UPC Table 12-8.

5_Resolved
2/M2.2     Provide the flow setting required to keep the HWC velocity below 5 FPS. (UPC 610.12.1)

6_Resolved
2/M3.2         Is it intended to insulate the rooftop gas piping? Please clarify.