T.I.: REMODEL FOR RESTAURANT. NEW FINISHES AND EQUIPMENT - TC
CONTRACTOR TO PAY INSPECTION FEES BEFORE PERMIT CAN BE ISSUED
Reviewed by: Bergstrom, Leigh W. Permit #: C15-1458
Phone: 343-8326 Date: 5/12/2015
Fax: 249-7615
Email: BergstromLW@muni.org
Permit Manager: Tommy Cornell
Phone: 343-8181
Email: CornellTA@muni.org
Project: Round Table Pizza
Review Number: 351412
STATUS: 4-29-15 Comments to be addressed. 5-12-15 APPROVED.
The following comments based upon the 2009 Uniform Plumbing Code must be resolved before a permit is issued. The approval of plans and specifications does not permit the violation of any section of the Uniform Plumbing Code or any federal, state or local regulations.
M2.1 The 3-compartment sink requires a center waste outlet (UPC 1001.2) with separate vented P-trap (UPC 1014.1.1).