DESIGN OF SCREWED ATTACHMENTS
Reference the calculations. Where the design of the screws is for combined tension and shear, it appears that the combined loading check has been taken as TD/T+VD/V < 1.2. Please provide substantiating documentation showing this equation is appropriate for combined tension and shear in a screw. AISI S100-07 section E4.5 appears to indicate a different equation. This equation deals specifically with combined shear and pull over. For other limit states please use the unity check unless there is documentation showing another method is appropriate.
Reviewed by: Bolen, Wayne A. Permit #: C14-1705
Phone: 343-8072 Date: 5/13/2015
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Romig Mechanical/Electrical Equipment Anchorage
Review Number: 350858
____________________________________________________________________________________
PERMIT STATUS
5/13/2015 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.
All submittals should be sent to the permit manager.