Permit Number: X15-1423
Permit Type: Commercial Building Permit - ChangeOrdr BldgAdd
Address: 2500 MINNESOTA DR Anchorage
Location:
Work Description: DEFERRED SUB:  vibration & seismic controls for HVAC / tb
Status: Closed
Project Name: Change Order of Bldg App C14-1705
Review Type: Structural
Result: Correction
Result Date: 5/14/2015 9:28:14 AM

Comments:

 Code SectionReview CommentStatus
1_

DESIGN OF SCREWED ATTACHMENTS

Reference the calculations. Where the design of the screws is for combined tension and shear, it appears that the combined loading check has been taken as TD/T+VD/V < 1.2. Please provide substantiating documentation showing this equation is appropriate for combined tension and shear in a screw. AISI S100-07 section E4.5 appears to indicate a different equation. This equation deals specifically with combined shear and pull over. For other limit states please use the unity check unless there is documentation showing another method is appropriate.






Advisory Information:

Reviewed by: Bolen, Wayne A.                                                  Permit #: C14-1705

Phone: 343-8072                                                                       Date: 5/13/2015

Fax: 249-7393

Email: BolenWA@muni.org

Permit Manager: Tony Barganier

Phone: 343-8339

Email: BarganierTA@muni.org

Project: Romig Mechanical/Electrical Equipment Anchorage

Review Number: 350858

____________________________________________________________________________________

 

PERMIT STATUS

5/13/2015 – Review complete. Comments issued.

 

Advisory Comment (no response required):  This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.

 

Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.

 

All submittals should be sent to the permit manager.

ADA Compliance      Privacy Statement & Disclaimer      Employee Search      eNewsletter      RSS