NEW OPENINGS IN CMU
ACI 530-08 section 1.17.3.2.3.1 requires vertical reinforcement of at least 0.2 square inches in cross sectional area within 16" of each side of an opening. Please verify that this reinforcement exists or provide details showing how this reinforcement will be provided if it does not exist.
Reviewed by: Bolen, Wayne A. Permit #: C14-1705
Phone: 343-8072 Date: 5/13/2015
Fax: 249-7393
Email: BolenWA@muni.org
Permit Manager: Tony Barganier
Phone: 343-8339
Email: BarganierTA@muni.org
Project: Romig Business Modifications
Review Number: 350857
____________________________________________________________________________________
PERMIT STATUS
5/13/2015 – Review complete. Comments issued.
Advisory Comment (no response required): This review is based on the requirements of the Anchorage Administrative Code (AAC), 2009 International Building Code (IBC), 2009 International Residential Code (IRC) and all adopted references thereto as amended by MOA. The following comments must be addressed before a permit can be issued. The approval of plans and specifications does not permit the violation of the codes, or any federal, state or local regulations.
Please provide a written response to the comments and include one copy of additional or revise calculations, and two copies of additional or revise drawings.
All submittals should be sent to the permit manager.